FAN COIL UNIT PIPING PACKAGES
GENERAL NOTES:
1. Nailor only recommends chilled water valve control for Nailor
Digital and Analog VAV control sequences where a constant
discharge temperature is maintained and humidity is therefore
controlled. Modulating cooling valve control with fixed fan
speed electric controls can increase relative humidity in the
space at part load conditions. Modulating heat valve control
may result in low leaving air temperatures while the valves
reduce flow as setpoint is approached. Nailor does not
recommend their use with standard controls for either
application.
2. All 39 Series Hi-Rise Units include two flexible stainless steel
briefed hoses and full port ball isolation valves per coil. This
hose/valve combination provides a “union” type connection to
allow coil removal. Hi-Rise Units require a Nailor supplied
piping package which is factory assembled, installed and
wired.
3. 35F and 37F Horizontal Units with Nailor Digital and Analog
VAV Controls require a Nailor supplied piping package. This
package (less optional ball valve) is factory assembled,
installed and wired in a full protective enclosure with access
door. Ball valves when selected as part of the package ship
loose for field connection.
4. All standard piping packages and components described in
this catalog are for chilled and hot water applications. They
may be also used with up to 50% ethylene and propylene
glycol solutions.
5. Control valve actuators are removable and may be serviced or
replaced without removal of the valve body. All control valves
are piped on the return side of the coil (3-way control valves
are mixing).
6. 2-position (spring return) chilled and hot water valve / actuators
are piped normally closed to the coil as standard. For hot water
coils, control valves are available normally open as an option.
This must be stated clearly on schedule/order.
7. All ball isolation valves on the return line are furnished with an
adjustable memory stop feature (when no other flow control
device is selected) and may be used as a balancing valve.
8. Pressure/Temperature (P/T) ports when selected are supplied
on the ball valves as standard. If it is required that P/T ports be
located to monitor the pressure and temperature directly
across the coil only, select PTO (other location) option.
9. Automatic fixed flow controls (FC, FCC) are available in the
following flow (GPM) ratings. Individual coil GPM requirements
must be specified on schedule/order.
1/2" (13) valve: 0.5 to 4.0 GPM in 0.5 GPM increments. 5 to 9
GPM in 1 GPM increments.
3/4" (19) valve: 3.0 to 4.0 GPM in 0.5 GPM increments. 5 to 12
GPM in 1 GPM increments.
10.
2-pipe system cooling and heating auto changeover systems
using a 2-way control valve include a 1/4" (6.3) bleed line to
assure proper changeover thermostat (Aquastat) operation.
11. The valve package piping and component details in the catalog
are for standard valves and components. Performance ratings
such as Cv, max. close-off pressure, operating temperature
and pressure are shown in component specifications.
Suitability for use must be based on individual application
requirements determined by others. Nailor assumes no
responsibility for selection and/or application of valve package
and components.
Basic System Types and Application:
All types may use a 2-way or 3-way motorized control
valve
2-Pipe System (One Valve Package)
A) Hydronic Cooling Only
B) Hydronic Heating Only
C) Hydronic Cooling and Heating (Aquastat required)
D) Hydronic Cooling with Total Electric Heat
E) Hydronic Cooling and Heating with Auxiliary Electric
Heat (Aquastat required)
4-Pipe System (Two Valve Packages)
A) Hydronic Cooling and Heating
Legend:
BV Ball Valves (2). Memory stop where required.
BVPT Ball Valves (2) with Pressure/Temperature (P/T)
Port. Memory stop where required.
FC Fixed Flow Control
FCC Fixed Cartridge Flow Control
AFS Adjustable Flow Circuit Setter
YS Y Strainer
YSB Y Strainer w/hose bib valve
PTO P/T Ports (other location)
BPV Bypass Balancing Valve