Engineered Comfort Fan Coil Controller EZstat Especificaciones Pagina 4

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 20
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 3
D4
8-20-07
FAN COIL UNIT CONTROLS
THE PROBLEM
High humidity at part load conditions has always been a
problem with traditional fan coil unit operation and will
become a greater factor in the selection of equipment by
design engineers in the future. Too much humidity and
comfort zone temperatures decrease to the point that
occupants feel chilled or clammy. This may also create
favorable conditions for mold and mildew growth.
As air moves across a cooling coil, the temperature of the
coil is normally below the dew point of the return air. This
causes the water in the air to condense on the coil surface
where it is gathered in a drain pan and disposed of through
drain lines. The air leaving a coil is typically about 55 to
60ºF. Since the temperature of the coil is usually below the
dew point of the entering air, water has been condensed
from the air and the air is very nearly saturated. This nearly
saturated air warms slightly as it moves through the duct to
the diffusers. By the time it exits into the room, it has risen
a degree or two in a typical system. It then mixes with the
room air and is again warmed, typically to about 74 – 78ºF
(23 – 26
ºC). Both air temperature and water content are
increased in the room; however, relative humidity levels
decrease because the warmer air is capable of holding
more water. The percentage compared to saturated air at
the higher temperature has decreased. See line A-B on the
attached psychometric chart.
THE SOLUTION
The attached sequence of operation (See Figure 2) and
psychometric chart (Figure 3), illustrate how the EPIC
control sequence utilizes variable air volume control, chilled
water valve modulation and constant discharge air
temperature to control a typical space using our unique
controls. Engineered Comfort has chosen 52ºF (11
ºC) as
the optimum discharge air temperature for fan coil
operation.
By lowering the discharge air temperature slightly, the
humidity levels in the room can be lowered. See line C-D
on the attached psychometric chart. This causes the
occupants to feel more comfortable at a slightly higher
temperature. The room temperature required to maintain
acceptable comfort can be raised by as much as 4ºF
(2.5
ºC). Most occupants will be more comfortable at the
increased temperature. This accomplishes five very
important results in addition to the energy and reheat
savings already provided by the ECM motor.
1. Lower relative humidity:
If the air volume and water to the coil are modulated to
maintain the discharge air temperature at all room
conditions as described in the EPIC control sequence,
room relative humidity levels decrease by 10 to 20%, and
there is less chance for wall sweating, which in turn lowers
the chances of mold growth. See line A-B vs. C-D on the
attached psychometric chart.
2. Higher comfort level temperature Setpoint:
The lowered relative humidity allows the occupant to reset
the room temperature higher by 1 – 4ºF (0.5 – 2.5
ºC), while
maintaining acceptable comfort levels. This in turn saves
energy due to higher room set points. (See Figure 1 printed
from ASHRAE Handbook, Fundamentals 2005, Chapter 8,
page 8.12)
Figure 1: ASHRAE Summer and Winter Comfort Zones
(Acceptable ranges of operative temperature and humidity for people
in typical summer and winter clothing during primarily sedentary activity.)
3. Increased chiller efficiency:
If the air volume and water to the coil are modulated to
lower flow during part load conditions, fan energy and
pumping energy is saved by taking advantage of room to
room building diversity on both the water and air sides of
the unit. Additionally, this holds the water and air in contact
longer at the coil allowing greater heat transfer from the air
to the water. This increases the return water temperature to
the chiller and decreases the required pumping energy
while increasing the efficiency of the chiller operation.
Consequently, the pipe sizes needed for the risers and any
duct run outs may be reduced. These reductions may offset
any additional first cost of the equipment.
4. Lower airflow and reduced fan energy cost:
If the supply air temperature is lowered using the EPIC
control sequence, less air from the fan coil is needed to satisfy
the room demand. The reduction in airflow can be
calculated as follows:
Variable Air Volume EPIC Fan Technology
®
Fan Coil Operation with
Constant Discharge Air Temperature
70
65
60
55
50
45
40
35
30
25
20
10
15
10
5
0
HUMIDITY PATIO, lb water vapor per 1000 lb dry air
OPERATIVE TEMPERATURE,
O
F
DEW-POINT TEMPERATURE,
O
F
60 65 70 75 80 85 90
100% rh
50% rh
60% rh
30% rh
Winter
Summer
68
O
F Wet Bulb
64
O
F Wet Bulb
CFM
1
x ΔT
1
= CFM
2
x ΔT
2
Where: CFM
1
= Airflow and ΔT
1
= EAT LAT for Std. FCU
CFM
2
= Airflow and ΔT
2
= EAT LAT for EPIC FCU
Therefore:CFM
2
= CFM
1
x
(
ΔT
1
)
ΔT
2
Vista de pagina 3
1 2 3 4 5 6 7 8 9 ... 19 20

Comentarios a estos manuales

Sin comentarios