Installation and Operation Manual
Fan Coil Controller – EZstat
EC-EZstat
Date: 9-2014 Supersedes: NEW
Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.
Page 26 of 36
Procedure Steps Display
Reset the
applicaon and
choose units of
measure.
Choosing an applicaon will reset the EZstat.
Adjust the PID
loops.
Choose LOOPS from the ADVANCED menu to adjust the values for
the cooling or heang PID loops. Only the proporonal and integral
properes can be changed from the display.
The proporonal default is 2° F.
The integral default is zero (0).






Enter or change
passwords.
Choose PASSWORDS from the ADVANCED menu to set either
Password 1 or Password 2. Note: Allow 60 seconds me elapse for
password change/setup to enable.
Password 1 is for a facility user and limits changes to acve
setpoints, fan operaon, occupancy, and heang and cooling
modes.
Password 2 is for a controls technician to set up and commission
the EZstat. When set, will lock user out from setpoints, fan
operaon, occupancy, and heang and cooling modes.
Entering four zeros (0000) removes the password. The EZstat is supplied
without passwords.
1. From the PASSWORD1 or PASSWORD2 menu either the or
buon to change the rst digit of the password.
2. Press the Enter buon to select the next digit. Repeat for all
four digits.
3. When the Enter buon is pressed for the last digit, the new
password is saved and the display advances.
Enter
PASSWORD1:
0 0 0 0
Calibrate the
inputs
Choose CALIBRATION from the ADVANCED menu to calibrate an
input. The EZstat includes two calibraon entries; one for the internal
temperature sensor and one for the oponal remote temperature
sensor connected to the RS terminal.
Enter a calibraon factor to adjust either input for sensor
inaccuracies.
For a low input reading enter a posive correcon value.
For a high input reading enter a negave correcon value.







Set the display
blanking.
Choose DISPLAY from the ADVANCED menu to set the display
appearance aer the last buon is pushed.
BLANKING—Choose one of the blanking
CLOCK—An analog clock replaces the temperature and
mode icons.
BACKLIGHT OFF—The display brightness changes to the
level set by DIM LEVEL aer the last buon interacon.
NONE—The temperature and mode icons always remain
visible.
DIM LEVEL—Sets the level of brightness of the display back light
if BACKLIGHT OFF is the selected blanking opon.








NOTE
NOTE