Installation and Operation Manual
Fan Coil Controller – EZstat
EC-EZstat
Date: 9-2014 Supersedes: NEW
Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.
Page 4 of 36
3.3 Specicaons
EZstat specicaons are subject to change without noce.
User Interface
The user interface is a color display and with ve push buons. Through the menu driven display, an operator can do the
following:
Add or change user passwords
Change setpoints
Set BACnet addressing
Set up and commission the installaon
Congure any available opons
Security
Separate passwords for users and controls technicians.
Display type
128 ×128 pixels
Acve color LCD with LED back lighng
0.98 x 1.04 inches (25 x 26 mm)
Inputs and outputs
All inputs and outputs are preprogrammed and applicaon specic. Review wiring label for proper connecons.
Analog inputs
Analog inputs represent BACnet analog input objects and are congured for discharge air temperature, remote
temperature sensor and water temperature sensor. Not all input sensors are applicable or required for all applicaons.
Sensors are automacally detected
Inputs accept industry‑standard 10,000 Ω, Type II (Nailor Part# H1‑1989) or Type III (Nailor Part# H1‑0246 and H1‑1764B)
thermistors sensors.
Input overvoltage protecon up to 24 VAC, connuous. 12‑bit analog‑to‑digital conversion
Analog outputs
Analog outputs are congured to represent BACnet analog objects. The outputs control modulang valves, and variable
speed fans, or other equipment that requires a proporonal input signal.
Short‑circuit protected
Loads up to 10 mA at 0–12 VDC
8‑bit PWM digital‑to‑analog conversion
Relay outputs
Relay outputs are congured to represent BACnet binary objects. The outputs control On/O valves, speeds for three‑
speed fans, fan start circuits, or electric heat.
All relay outputs are normally open, SPST, Form “A” relays
1 ampere maximum per relay at 24 VAC or VDC for each output. Maximum for all relay outputs is 3 amperes (72VA).
Connectors
Screw terminal block mounted to back plate
Wire size 14‑22 AWG
Communicaons—BACnetMS/TP
Integral peer‑to‑peer BACnet MS/TP network communicaons. Network speeds from 9600 to 76,800 baud.
Front panel congurable device instance, MAC address, and baud. Automac baud detecon, see the topic Set up the
communicaon. Screw terminal block mounted to back‑plate. Wire size 14–22 AWG
Meets or exceeds ANSI/ASHRAE BACnet Standard 135‑2008 for Applicaon Specic Controllers