Installation and Operation Manual
Fan Coil Controller – EZstat
EC-EZstat
Date: 9-2014 Supersedes: NEW
Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.
Page 27 of 36
Procedure Steps Display
User lockout
buons
Choose KEY LOCKOUT from the ADVANCED menu to limit accessibility to
users with Password 1, the user password.
MODE/SETPOINTS—Users with Password 1 cannot change any
value or mode.
MODE—Users with Password 1 cannot change the heang/
cooling, fan, or occupancy modes.
NONE—Users with Password 1 have full access to acve
setpoints, heang/cooling, fan, and occupancy modes.





7 SEQUENCES OF OPERATION
Topics in this secon cover the sequences of operaon for the EZstat. These are advanced topics for control’s technicians and
engineers.
This secon covers the following sequences of operaon:
Setpoint Limits
Occupancy
Automac cooling and heang changeover
Scheduling occupancy
Display blanking and backlight
Temperature sensing inputs
PID control loops
Valve operaon for fan coil units
Fan operaon for fan coil units
7.1 Setpoint Limits
The programming in the EZstat will limit the setpoint entry so that no heang setpoint is set higher than its corresponding
cooling setpoint.
If a user is adjusng a setpoint and it falls within the range set by the value of Minimum Setpoint Dierenal, the
corresponding setpoint will be changed to maintain the dierenal. For example, the Minimum Setpoint Dierenal is
F and the Occupied Heang setpoint is 70° F. If the user lowers the Occupied Cooling setpoint to 71° F, the controller
recalculates the Occupied Heang setpoint and changes it to 67° F.
7.2 Occupancy
The EZstat is designed to operate as a stand‑alone controller and can determine occupancy based on its internal occupancy
schedule. The EZstat can be in any one of the following occupancy states.
OCCUPIED
UNOCCUPIED
The occupancy and standby states can also be commanded by another BACnet device or an operator workstaon
connected to the building automaon network.
Occupied
In controllers without a moon sensor, the EZstat starts in the occupied state. If the internal schedule is enabled, the state
of the schedule is set to either OCCUPIED or UNOCCUPIED as the inial state.
Unoccupied
The controller changes to the UNOCCUPIED state only if the internal occupancy schedule is enabled and if the schedule is
inacve.